Allen-Bradley ControlLogix Manuale Utente Pagina 130

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 212
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 129
130 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 8 I/O Modules
Add Remote I/O to the I/O Configuration
If you are adding remote I/O, add the I/O modules to the backplane of the
remote communication module that is connected to the controller. To add a
remote I/O to the I/O Configuration folder in the Logix Designer application,
complete these steps.
1. Add a communication module to the backplane that contains the
controller.
2. Specify the communication module properties according to your network
configuration.
For more information about the communication module and network
properties, see the Additional Resources
section in the preface.
3. Right-click the communication network and choose New Module.
4. Add the remote communication module that you are using.
Vedere la pagina 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 211 212

Commenti su questo manuale

Nessun commento